Switch to mobile site
Loading

Maintenance and Service

Exam revision materials for Plumbing Level 2&3 and ACS Gas Safety test

Create an Article

Boilers

Baxi

Click to show/hide index

Showers

Aqualisa

Bristan

Crosswater

Crosswater

Grohe

HUB-001A-WAX Vado Thermostatic Cartridge

Hansgrohe

Hudson Reed

IB

Mira

Porcelanosa

S960134NU Thermostatic Cartridge

Sirrus Rothwell R995 Antique Shower

Trevi

Triton

Triton

Ultra

Vola

Boilers

Alfa Laval

Alpha

Ariston

Baxi

Biasi

Chaffoteaux

Electroheat PLC

Ethos

Ferroli

Glowworm

Halstead

Heat Lline

Ideal

Keston

Main

Myson

Nibe

Potterton

Saunier Duval

Vaillant

Viessmann Vitodens 100 W Compact

Vokera

Worcester

Taps

Armitage Shanks

Grohe

Hansgrohe

Mayfair

Phoenix

Space Heaters

Baxi

Remeha

Bathstore Thermostatic Cartridge

Servicing Guide

Pumps

Grundfos

Thermal Store Cylinders

Pulsacoil

Underfloor Heating

PolyPlumb

Toilets

Geberit

Grohe

Hot Water Cylinders

Dimplex

Megaflow

Santon

Gas Safety Inspection

Gas Flue Analysers

Gas Hobs

AGA

Neff

Baxi Duo-Tec Combi HE - Faulty pressure sensor 5114748

Boiler displays error code E1

Replace or clean the pressure switch 5114748

< Go Back2016-03-25

Baxi Combi 80e - Domestic hot water diaphragm

Baxi Combi 80e - Domestic hot water diaphragm is perished and need replacement. The heating is working fine but there is no hot water.

  • Open a hot water tap and look at the flow sensor pin should move forward and press the microswitch to fire up the boiler
  • If the pin doesn't move then diaphragm need replacement
  • The replacement part is 248066
< Go Back2013-11-09

Baxi Solo 2 PF50 - PCB replacement

Baxi Solo 2 PF 50 boiler once and gain stops working. The fan is running, the gas valve is opened but there is no spark occurring occasionally.

< Go Back2013-10-27

Baxi Combi 105HE - loosing pressure fast

Baxi Combi 105HE boiler is loosing pressure very fast. First of all check that the filling loop which supposed to top up the central heating system with water was closed. Then you should check the expansion vessel charge it should be around 1bar. If there is no charge or water is coming when you pressed the nipple then replace or recharge it with the pump up to 1.5 bar. Top up the system up to 2 bar and watch the pressure discharge pipe outside the property if its constantly dripping or pouring water then Pressure Relief Valve have to be replaced. The part number is 248056 and you can order it from here. To replace this part you don't need a gas engineer.

Baxi Combi 105HE manual: PDF

< Go Back2013-03-16

Baxi Brazilia F8S

Balanced flue gas wall heater Baxi Brazilia F8S brocken control knob. For this particular model F8S you will need a long version of the control knob. The replacement part number is Baxi 234643 control knob assembly. To replace this part you don't need a gas engineer. In order to fit the replacement part correctly simply remove the casing by pulling it upwards. You can order it from here.

Wall heater manual: PDF